Leave Your Message

PSD-70E 112V External Shed glass insulator

Подвесной стеклянный изолятор ПСД 70Е 112V

Designed for isolating and securing wires and lightning protection ropes on overhead power transmission lines (OPL), as well as in distribution devices of AC power stations and substations with voltages above 1000 V and frequencies up to 100 Hz.

U70BL-280-146-450 4.jpg

  • Brand: QOCI (QX)
  • Catalog ID: UG70B146/450D
  • Type: Double-Shed Type
  • Material: Glass Dielectric ,Hot-dip Galvanized Cast Iron Cap & Forged Steel Pin
  • Place of Origin: Jiangxi

Product Information

IEC Stand :PSD-70E 112V


P (П) Disc Suspension (type of insulator)

S  (С) Glass (insulating material)

D  (Д) Double‑skirt / two‑rib (configuration of the insulating part)

70 Minimum mechanical failing load, 70kN

E Modernization index of the insulator

112 large height  (146mm)/alkaline glass/Regular pin

111 large height (146mm)/alkaline glass/pin with zinc sleeve

V R-Split pin

double shed glass Insulator.jpg

  

Dimensional data


Spacing(S)

146mm

Diameter(D)

280mm

Creepage distance (L)

450mm

Socket coupling

16A

Mechanical values


Mechanical failing load

70kN

Mechanical residual strength

56kN

Electrical Values


Wet power frequency withstand voltage

45kV

Dry lightning impulse withstand voltage

120kV

Power frequency puncture voltage

110kV

Radio-influence Voltage


RIV test voltage rms to ground

Maximum RIV at 1000 kHz:

10 kV

50 μV


Corona visual lest P/C

18/22 KV


Power frequency electric arc voltage

0.12s/20kA


Packing information


Net weight

5.4kg

Crate Quantity:

5/6/7pcs

     .

Industry Standard(s)


Manufactured accordance with GOST 6490-2017,IEC60383-1:1993,60305,GB/T1001.1